The 3RT1034-3XB40-0LA2: Screw-type terminals on the main circuit accept stranded conductors up to 2x 25 mm² and solid up to 2x 2.5 mm², which covers the feed and motor cable for the full rated load without needing lug adapters. The auxiliary contact block is rated 10 A at 24 VDC, 6 A at 230 VAC, and 3 A at 400 VAC — enough for a PLC input or a holding-circuit interlock. Arcing time runs 10–15 ms, and DC operating time is 20–30 ms — both within the range for standard motor starter coordination.
Clearance requirements: 10 mm upwards, downwards, forwards, and to the side — standard for S2 frame spacing in a 55 mm wide footprint.