The 3RT1035-1AC20-ZW96: The AC-3 motor power ratings tell you what it can actually start and run: 22 kW at 500 V, 18.5 kW at 400 V, and 11.4 kW at 690 V. The AC-4 rating (300 switching cycles per hour maximum) governs reversing or inching duty; if your application jogs the motor repeatedly, that's the limit that matters, not the AC-3 figure. Mechanical life is listed at 10 million operations typical, so it's not a wear-item concern in normal cycling service. The auxiliary contact block handles 10 A at 24 V, 6 A at 230 V, and 0.3 A at 220 V — enough for PLC inputs or relay coils in the same panel.
Front enclosure is IP20 (finger-safe), terminal area is IP00 — wire terminations need to be inside a cabinet or guarded.