Rated 18.5 kW at AC-2 duty at 400 V, and 35 A at AC-4 at 400 V.
RoHS compliance date is noted as 05/01/2012, and the substance prohibitance date aligns with EU RoHS requirements.
Dimensions: 112 mm height, 55 mm width, 164 mm depth. Main circuit terminals accept solid wire 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), max 2x (0.75 to 4 mm²). Side-by-side mounting permitted without derating for the thermal stack-up.
Switching performance
Arcing time 10 to 15 ms, with AC switching times of 7 to 20 ms. Mechanical life typical 10 million operations. Maximum operating rates: 1,200 cycles/hour at AC-1, 600 at AC-2, 1,000 at AC-3, 300 at AC-4. Auxiliary contact ratings: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V. The 24 V rating is the one to watch for PLC-level control circuits.