Skip to main content
Siemens 3RT1035-1AL00 — Contactors

Siemens 3RT1035-1AL00 SIRIUS Power Contactor, Size S2, 22 kW

MPN3RT1035-1AL00

Siemens SIRIUS power contactor, 3RT1035-1AL00, Size S2, screw-type terminals, 22 kW at 400 V AC-3, 55 mm width, DIN EN 50022 rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1035-1AL00 — Identification
ParameterValue
Contactor frame sizeS2
3RT1035-1AL00 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V35 A
Rated value @ 400 V3 A
Rated value @ 500 V22 kW
Rated value @ 690 V11.4 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1035-1AL00 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz125 V
3RT1035-1AL00 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1035-1AL00 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 125 A
Short-circuit coordination type 2, fusefuse gL/gG: 63 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1035-1AL00 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, solid or stranded2x (0.75 ... 16 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Side-by-side mountingYes
3RT1035-1AL00 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1035-1AL00 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT1035-1AL00 — Mechanical
ParameterValue
Width55 mm
Height112 mm
Depth115 mm
3RT1035-1AL00 — Specifications
ParameterValue
At AC7 ... 20 ms

Product details

SIRIUS Power Contactor for Motor Loads

Its primary motor ratings are 22 kW at 400 V and 11.4 kW at 690 V under AC-3 duty, which covers the majority of standard squirrel-cage motor starting and stopping applications. Side-by-side mounting is supported, allowing dense packing in multi-contactor assemblies. Main power circuit connections use screw-type terminals, accepting stranded conductors up to 2x 25 mm² and solid conductors up to 2x 4 mm².

Rating Depth and Application Fit

The AC-3 rating of 22 kW at 400 V defines the contactor's capability for switching three-phase induction motors under normal running conditions — starting, stopping, and occasional inching. For resistive or lightly inductive loads (AC-1), the contactor's thermal current capacity is not directly stated, but the AC-2 rating of 18.5 kW at 400 V indicates suitability for slip-ring motor starting. The maximum operating rate at AC-3 is 1,000 switching cycles per hour, which aligns with typical conveyor and pump cycling. Auxiliary contact ratings are provided for DC switching: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V. These values are critical for control circuit designers sizing pilot devices or PLC outputs feeding the contactor coil.

Environmental and Compliance Profile

No UL or CSA listing is explicitly stated in the available data, but the SIRIUS platform typically carries these approvals; verification against the specific project's certification requirements is recommended before specifying.

Dimensions are 112 mm height, 55 mm width, and 115 mm depth, fitting standard 55 mm-wide contactor slots in panel layouts. Wire termination accepts solid conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and max 2x (0.75 to 4 mm²). Stranded conductors: 2x (0.75 to 25 mm²). This range covers standard motor feeder cables up to 6 mm² for the 22 kW rating, with flexibility for paralleled control wiring.

Frequently asked questions

What is the closest functional alternative to 3RT1035-1AL00?

The 3RT1036-1AB00 is a peer in the same SIRIUS family, but it uses a different coil voltage and may have different auxiliary contact configurations. Verify the coil rating and terminal layout before substituting in an existing panel design.

MPN
3RT1035-1AL00