Its 24 VDC coil holds at 10 A and drops out below 18 V — standard for PLC-driven 24 V control buses. The AC-3 rating of 22 kW at 500 V tells you it handles standard three-phase induction motors up to that power; at 690 V the same contactor is rated 11.4 kW, so the voltage derating is already baked in. At AC-3 the switching rate is 1,000 operations per hour; at AC-4 it is 300 per hour.
DIN rail fit and wiring
The S2 frame footprint is 55 mm wide, 112 mm high, and 130 mm deep. The terminal enclosure is rated IP00, meaning the connection points are not sealed — the front face carries IP20 for finger-safe touch protection once wired. The minimum wire size at 40 °C is 16 mm² — that's the smallest conductor that carries the full rated current without exceeding the terminal temperature rise.
