The 48 VDC coil pulls in with a typical arcing time of 10 to 15 ms and a DC dropout delay of 20 to 25 ms — fast enough for most sequencing but worth noting if your safety circuit needs a defined off-delay. Rated for AC-3 motor switching at 400 V, it delivers 18.5 kW, and at 500 V it handles 22 kW.
The S2 footprint is 55 mm wide, 112 mm tall, 130 mm deep. The minimum permissible conductor at 40 °C is 16 mm² — that's the thermal limit, not a wiring convenience.