Rated for AC-3 duty at 22 kW on 500 V and 18.5 kW at 400 V, it also carries an AC-4 rating of 35 A at 400 V for reversing or inching applications. The contactor handles resistive loads up to AC-1 maximum switching frequency of 1 200 operations per hour.
Terminal and environmental specs
Main current circuit terminals are screw-type, accepting solid conductors up to 2x 2.5 mm² and stranded up to 2x 25 mm². Pollution degree 3 means it withstands conductive pollution typical of industrial enclosures.
Auxiliary contact ratings
The integrated auxiliary contacts are rated for 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V AC, covering control-circuit switching across common panel voltages.