Rated for AC-4 duty at 35 A and 400 V, this contactor handles the severe switching conditions of motor reversing or plugging — where the contacts make and break locked-rotor current. For standard motor starting (AC-2), it carries 18.5 kW at 400 V, and at 500 V it delivers 22 kW, with a 690 V rating of 11.4 kW. The front face is IP20, while the terminals are IP00 — standard for panel-mounted contactors where the enclosure provides the overall protection. Pollution degree 3 suits industrial environments with conductive contamination. Side-by-side mounting is permitted, which simplifies multi-contactor panels.
Main circuit screw terminals accept 2x (0.25 to 2.5 mm²) solid or 2x (0.75 to 25 mm²) stranded wire. The auxiliary circuit accepts 2x (0.75 to 16 mm²) solid or stranded. This range covers standard panel wiring from signal-level to motor power conductors.