Depth is 115 mm, width 75 mm, height 112 mm — check your enclosure depth clearance if you're swapping into an existing panel, especially one originally laid out for a shorter contactor.
For AC-3 (squirrel-cage motors, normal start/run), the rating at 500 V is 22 kW, and at 690 V it's 11.4 kW. The contactor is rated for 60 Hz operation, with a rated control supply voltage of 230 V at 60 Hz. Maximum switching rates vary by duty: 1200 cycles/hour for AC-1 (resistive), 1000 for AC-3, and 300 for AC-4 — the AC-4 figure governs if you're doing frequent reversing.
Solid wire accepts 2x (0.25 to 2.5 mm²), stranded accepts 2x (0.75 to 25 mm²). At 40 °C ambient, the minimum permissible conductor cross-section is 16 mm² — that's the thermal limit for continuous current, not the mechanical minimum.
RoHS compliance date is May 1, 2012 — the part meets the EU RoHS substance restrictions from that date forward.