Siemens 3RT1036-1AG24-ZX95 — SIRIUS Size S2 Power Contactor
It mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 50022, with a footprint of 55 mm width by 112 mm height by 164 mm depth — the 164 mm depth is the dimension to account for when planning gland-plate clearance or enclosure depth.
Motor Ratings and Duty Cycles
Rated motor power at 500 V reaches 30 kW, and at 690 V it delivers 11.4 kW. The AC-3 maximum switching rate is 800 operations per hour, while AC-4 (plugging / inching) is limited to 300 per hour.
DC Switching Capability and Coil Data
For DC loads, the contactor switches 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V. The coil operates at 50/60 Hz with a voltage tolerance of 0.8...1.1 x rated at 50 Hz and 0.85...1.1 at 60 Hz.
Solid wire accepts 2x (0.5...1.5 mm²), 2x (0.75...2.5 mm²), and max 2x (0.75...4 mm²). Stranded wire range is 2x (0.75...25 mm²). Solid or stranded combined accepts 2x (0.75...16 mm²). The terminal protection rating is IP00; the front of the contactor is IP20.