The 690 V rated insulation voltage covers most 400 V and 480 V line-to-line systems with headroom for grounded-wye configurations. The S2 frame size determines the physical footprint and the maximum contactor current — expect this to handle motor currents typical of a 30 kW load at 500 V or 11.4 kW at 690 V. Screw-type terminals on the main circuit accept solid conductors from 2x 0.5 mm² up to 2x 4 mm² and stranded up to 2x 25 mm². That's enough for most motor feeder cables up to 6 AWG. The IP20 front means it's finger-safe once installed in a closed panel; the terminal area itself is IP00, so live parts are exposed during wiring — standard for panel-mount contactors. Mechanical life is typical at 10 million operations. Switching frequency ranges from 300 cycles/hour at AC-4 (the toughest motor inching/jogging duty) up to 1,000 cycles/hour at AC-1 (resistive loads). For a motor-starting application (AC-3), expect 800 cycles/hour.

Siemens 3RT1036-1AP00-ZW98 SIRIUS Power Contactor, S2, 690 V
Siemens SIRIUS power contactor, size S2, 3RT1036-1AP00-ZW98, rated insulation voltage 690 V, screw-type terminals, snap-on mounting.
Specifications
| Parameter | Value |
|---|---|
| Contactor frame size | S2 |
| Parameter | Value |
|---|---|
| Rated operational current, AC-4 @ 400 V | 41 A |
| Rated value @ 400 V | 3 A |
| Rated value @ 500 V | 30 kW |
| Rated value @ 690 V | 11.4 kW |
| Rated value @ 230 V | 6 A |
| Rated value @ 24 V | 10 A |
| Rated value @ 60 V | 2 A |
| Rated value @ 110 V | 1 A |
| Rated value @ 220 V | 0.3 A |
| Parameter | Value |
|---|---|
| Control supply voltage type | AC |
| Rated value @ 50 Hz | 0.8 ... 1.1 |
| Rated value @ 50 Hz | 230 V |
| Parameter | Value |
|---|---|
| Main poles | 3 |
| Main NO contacts | 3 |
| Auxiliary contact reliability | 1 faulty switching per 100 million (17 V, 1 mA) |
| Parameter | Value |
|---|---|
| Short-circuit coordination type 1, fuse | fuse gL/gG: 160 A |
| Short-circuit coordination type 2, fuse | fuse gL/gG: 80 A |
| Aux. switch short-circuit protection, fuse | fuse gL/gG: 10 A |
| Parameter | Value |
|---|---|
| Main circuit connection | screw-type terminals |
| Conductor cross-section, solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²) |
| Conductor cross-section, finely stranded w/ ferrule | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| Side-by-side mounting | Yes |
| Parameter | Value |
|---|---|
| Durability (operating cycles, typ.) | 10 000 000 |
| Durability with aux. switch block (cycles, typ.) | 10 000 000 |
| Parameter | Value |
|---|---|
| Operating temperature range | -25 ... +60 °C |
| Storage temperature range | -55 ... +80 °C |
| Parameter | Value |
|---|---|
| Width | 55 mm |
| Height | 112 mm |
| Depth | 115 mm |
| Parameter | Value |
|---|---|
| At AC | 7 ... 20 ms |
Product details
Frequently asked questions
What is the closest functional second-source?
The Siemens 3RT1036-1AB00 is a direct sibling in the same S2 frame size. The key difference is the coil voltage — the -1AP00 variant uses a different coil rating than the -1AB00. Verify coil voltage compatibility before substituting.
What is the depth of this contactor?
The depth is 115 mm. Combined with a width of 55 mm and height of 112 mm, it fits a standard 55 mm wide DIN-rail slot.
What wire sizes does the screw terminal accept?
Solid conductors: 2x 0.5 to 1.5 mm², 2x 0.75 to 2.5 mm², max 2x 0.75 to 4 mm². Stranded: 2x 0.75 to 25 mm².
Will this drop into a panel designed for 3RT1036-1AB00?
Yes, same S2 frame size and mounting footprint. The physical dimensions and terminal layout are identical. The only difference is the coil — check that the coil voltage matches your control circuit.