It carries a 22 kW rating at 400 V in AC-2 duty (slip-ring motors), and 41 A in AC-4 (reversing/inching). At 500 V it handles 30 kW, and at 690 V it handles 11.4 kW — so it covers standard 400 V and 500 V three-phase motor circuits across a range of induction and wound-rotor machines.
Depth is 130 mm — check gland-plate clearance if the panel is shallow.
Terminal wiring and conductor sizing
Accepts solid wire from 2x 0.5 mm² up to 2x 4 mm², and stranded wire from 2x 0.75 mm² up to 2x 25 mm².
Switching performance and life
Maximum switching rates: 1,000 ops/hr in AC-1 (resistive), 800 in AC-3 (standard motor starting), 400 in AC-2, and 300 in AC-4 (plugging/reversing). DC arcing time is 20 to 25 ms.
DC switching capability