It carries a 30 kW rating at 500 V in AC-3 duty, and 11.4 kW at 690 V — the AC-3 figure is the one that governs motor starts under load, so that 500 V, 30 kW line is what you size the contactor against for a standard induction motor.
Main circuit terminals are screw-type, accepting solid wire from 2x 0.5 to 4 mm² and stranded up to 2x 25 mm². The front of the contactor is IP20 — finger-safe for panel access; the terminal area itself is IP00, meaning the wiring zone is open and needs enclosure protection against dust and accidental contact.
Coil pickup at 50 Hz is 0.8 to 1.1 times rated voltage; dropout on DC takes 20 to 25 ms. Shock resistance is 15 g for 5 ms and 8 g for 10 ms on AC — enough for panel-mounted gear in conveyor or pump stations that see vibration from adjacent machinery.
Switching frequency and auxiliary ratings
Maximum switching rates: 1000 ops/h for AC-1 resistive loads, 800 ops/h for AC-3 motor duty, 400 ops/h for AC-2, and 300 ops/h for AC-4 reversing duty. The auxiliary contact ratings cover 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 0.3 A at 220 V — these are the values for the built-in auxiliary block, so verify your control voltage against the curve before wiring.