Skip to main content
Siemens 3RT1036-1XX10-0AA8 — Contactors

Siemens SIRIUS 3RT1036-1XX10-0AA8 Power Contactor, S2 Size,

MPN3RT1036-1XX10-0AA8

Siemens SIRIUS power contactor, S2 size, 3RT1036-1XX10-0AA8, screw-type terminals, 55 mm width, AC-3 rated 30 kW at 500 V, snap-on DIN rail mounting.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1036-1XX10-0AA8 — Identification
ParameterValue
Contactor frame sizeS2
3RT1036-1XX10-0AA8 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V41 A
Rated value @ 400 V3 A
Rated value @ 500 V30 kW
Rated value @ 690 V11.4 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1036-1XX10-0AA8 — Control & Coil
ParameterValue
Control supply voltage typeAC
3RT1036-1XX10-0AA8 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1036-1XX10-0AA8 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 160 A
Short-circuit coordination type 2, fusefuse gL/gG: 80 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1036-1XX10-0AA8 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, solid or stranded2x (0.75 ... 16 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Side-by-side mountingYes
3RT1036-1XX10-0AA8 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1036-1XX10-0AA8 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT1036-1XX10-0AA8 — Mechanical
ParameterValue
Width55 mm
Height142 mm
Depth130 mm
3RT1036-1XX10-0AA8 — Specifications
ParameterValue
At AC15g / 5 ms, 8g / 10 ms

Product details

Siemens SIRIUS 3RT1036-1XX10-0AA8 Power Contactor

Rated for AC-3 duty at 30 kW at 500 V and 11.4 kW at 690 V, this contactor handles the typical motor starting and running currents for pumps, fans, and compressors in that power band. The contactor measures 55 mm wide by 142 mm high by 130 mm deep, fitting into a standard S2 footprint on the DIN rail.

The AC-3 rating of 30 kW at 500 V is the key selection figure for a standard squirrel-cage motor load. At 400 V, the AC-3 rating is not explicitly stated in the evidence, but the AC-2 rating at 400 V is 22 kW, which covers slip-ring motor starting. The AC-1 maximum switching frequency is 1,000 operations per hour, while AC-3 allows 800 per hour and AC-4 drops to 300 per hour — these limits govern the duty cycle in high-speed applications like conveyor indexing. For DC switching, the contactor is rated at 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V. These are the make-and-break capacities for DC loads, which are significantly lower than AC due to the lack of a natural current zero crossing. This covers most panel wiring from control circuits to main power feeders.

The part carries a RoHS compliance date of May 1, 2012, confirming it meets the EU Restriction of Hazardous Substances directive for the current production batch. The substance prohibitance date indicates the design was verified compliant as of that date.

The S2 size footprint is shared across the SIRIUS 3RT1 and 3RT5 families, so the panel cutout and rail position are consistent. Side-by-side mounting is allowed, which means no gap is required between adjacent contactors for thermal reasons.

Frequently asked questions

What wire sizes does the 3RT1036-1XX10-0AA8 terminal accept?

The screw terminals accept solid conductors from 2x (0.5 to 1.5 mm²) up to 2x (0.75 to 4 mm²), and stranded conductors from 2x (0.75 to 25 mm²).

MPN
3RT1036-1XX10-0AA8