Skip to main content
Siemens 3RT1036-3AN60 — Contactors

Siemens 3RT1036-3AN60 SIRIUS Power Contactor, 22 kW AC-2

MPN3RT1036-3AN60

Siemens SIRIUS power contactor, size S2, 3RT1036-3AN60, 22 kW at AC-2 400 V, screw-type terminals, 55 mm wide, snap-on DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1036-3AN60 — Identification
ParameterValue
Contactor frame sizeS2
3RT1036-3AN60 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V41 A
Rated value @ 400 V3 A
Rated value @ 500 V30 kW
Rated value @ 690 V11.4 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1036-3AN60 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz200 V
3RT1036-3AN60 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1036-3AN60 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 160 A
Short-circuit coordination type 2, fusefuse gL/gG: 80 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1036-3AN60 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid2x (0.25 ... 2.5 mm²)
Conductor cross-section, solid or stranded2x (0.75 ... 16 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.25 ... 1.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Side-by-side mountingYes
3RT1036-3AN60 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1036-3AN60 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT1036-3AN60 — Mechanical
ParameterValue
Width55 mm
Height112 mm
Depth115 mm
3RT1036-3AN60 — Specifications
ParameterValue
At AC7 ... 20 ms

Product details

Its headline rating is 22 kW at AC-2 duty at 400 V — that's the current it can make and break for slip-ring motors or wound-rotor applications where the starting current is moderate. At 55 mm wide, it fits alongside other SIRIUS components without eating up rail space. Terminals are screw-type on the main current circuit, accepting 2x (0.75... 25 mm²) stranded or 2x (0.25... 2.5 mm²) solid. That covers most panel wiring up to 25 mm² for the power legs.

AC-2 duty means it's rated for starting and stopping wound-rotor motors where the inrush is controlled; if you're switching a standard squirrel-cage motor, you'd look at the AC-3 rating (not listed here, but typically lower for the same frame). The mechanical life of 10 million operations means it'll outlast most panel rebuild cycles. Storage range extends to -55 to +80 °C, so it's fine for unheated warehouses. IP20 on the front (finger-safe), IP00 at the terminals — so the wiring zone needs to be inside a locked enclosure or guarded.

Frequently asked questions

What's the closest alternative — 3RT1036-1AB00?

The 3RT1036-1AB00 is the same SIRIUS size S2 contactor but with spring-cage terminals instead of screw-type. It drops into the same footprint and wiring pattern — the main difference is the termination method, so choose based on your panel's wire preparation preference.

What is the depth of this contactor?

The depth is 115 mm. That's the dimension from the DIN rail mounting surface to the front of the contactor — important for enclosure depth clearance.

What wire sizes does the screw terminal accept?

For stranded wire, it accepts 2x (0.75... 25 mm²). For solid wire, 2x (0.25... 2.5 mm²). That covers most power and control wiring in industrial panels.

Will 3RT1036-3AN60 drop into a panel specified for 3RT1036-1AB00?

Yes — same frame size S2, same 55 mm width, same snap-on DIN rail mounting. The only difference is the terminal type: screw vs. spring-cage. No rewiring of the main circuit is needed if your lugs match screw terminals.

MPN
3RT1036-3AN60