The coil is rated at 42 V at 50 Hz, with an operating range of 0.8 to 1.1 times the rated voltage at 50 Hz. This is a specific voltage variant — not the common 24 V or 230 V — so verify your control voltage matches before specifying. For motor duty, the contactor is rated 37 kW at 400 V in AC-3 category (squirrel-cage motors, starting and disconnecting running), and 30 kW at 400 V in AC-2 (slip-ring motors, starting and switching off). In AC-4 duty (inching, plugging, reversing) it handles 55 A at 400 V — the most demanding thermal cycle, so that figure governs applications with frequent jogging.
The contactor occupies 70 mm width, 146 mm height, and 139 mm depth — a compact S3 footprint. Side-by-side mounting is permitted, which saves rail space in dense panels. The main current circuit uses screw-type terminals; solid wire accepts 2x (0.25 to 2.5 mm²), stranded accepts 2x (10 to 50 mm²), and a mixed solid-or-stranded range of 2x (2.5 to 16 mm²) covers most panel wiring. Pollution degree 3 (conductive pollution) means it is suited for industrial environments where occasional condensation or light contamination occurs. Mechanical endurance is rated at 10,000,000 operating cycles typical, with switching rates up to 1,000 cycles per hour for AC-1 and AC-3, 400/h for AC-2, and 300/h for AC-4.
The part carries a RoHS substance prohibition date of 05/01/2012, confirming compliance with the EU RoHS directive for the materials in the bill of materials.