It's rated for 30 kW at 400 V in AC-2 duty (slip-ring motors, moderate inrush), and 37 kW at 500 V in AC-3 duty (standard squirrel-cage motors). The AC-4 rating of 55 A at 400 V covers reversing and inching applications with high electrical stress on the contacts.
Wiring and terminations
Main current circuit uses screw-type terminals. Solid conductors accept 2x (0.25 to 2.5 mm²) for control wiring, while stranded power cables take 2x (10 to 50 mm²). The auxiliary contacts (not detailed here) share the same terminal style, so keep a common screwdriver bit on the panel.
RoHS compliance date is noted as May 1, 2012, covering the EU directive.