For standard motor starting (AC-3 duty), it is rated at 37 kW at 500 V, and 30 kW at 400 V under AC-2 duty for slip-ring motors. The main current circuit uses screw-type terminals, accepting 2x (0.25...2.5 mm²) solid or 2x (10...50 mm²) stranded conductors.
The enclosure front carries an IP20 rating with a cover or box terminal; the terminal area itself is IP00, so the panel design must provide supplementary protection against accidental contact with live conductors.