Its headline ratings are 37 kW at AC-2 duty (400 V) and 66 A at AC-4 duty (400 V) — the AC-2 figure governs slip-ring motor starting, while AC-4 covers plugging and inching, so this part handles heavy reversing or jogging applications without derating.
Dimensions are 70 mm wide, 146 mm high, 139 mm deep, so it occupies a standard S3 footprint. Side-by-side mounting is permitted, which saves rail space when grouping multiple contactors.
Terminals and wiring
Accepts solid conductors 2x (0.5... 1.5 mm²), 2x (0.75... 2.5 mm²), max. 2x (0.75... 4 mm²), and stranded conductors 2x (10... 50 mm²). IP20 on the front with cover or box terminal; the terminal itself is IP00 — so panel builders should plan for enclosure protection if the contactor is exposed.
Degree of pollution 3, meaning it tolerates conductive pollution in industrial environments. RoHS compliance date listed as 05/01/2012.