The screw-type terminals on the main current circuit accept solid conductors from 2x (0.25... 2.5 mm²) and stranded conductors up to 2x (10... 50 mm²), covering a wide range of motor feeder cables.
Rated at 45 kW at 500 V AC-3 and 21.1 kW at 690 V AC-3, this contactor handles standard three-phase induction motors up to those power levels. The maximum mechanical switching frequency at AC-3 is 1 000 operations per hour, adequate for most conveyor and pump cycles.
Environmental and protection specs
IP20 on the front with the cover or box terminal installed; the terminal area itself is IP00, so the contactor must be mounted inside an enclosure that provides the required system IP rating.