It's rated for 55 kW at 500 V in AC-3 duty, which covers the majority of three-phase induction motor starts across pumps, fans, and conveyors. The 45 kW at 400 V AC-2 rating handles slip-ring or wound-rotor motors where the load is switched under reduced current.
Depth is 188 mm, so check your enclosure depth before panel layout.
Built-in auxiliary contacts are rated at 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V. For DC switching, the ratings drop to 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V — the DC arc extinction is harder, so stay within these limits for PLC or relay coil loads.