3RT1054-1AD36 — Identification
ParameterValue
Contactor frame sizeS6
3RT1054-1AD36 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V97 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V25 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1054-1AD36 — Control & Coil
ParameterValue
Control supply voltage typeAC/DC
Rated value @ 50 Hz0.8
Rated value @ 50 Hz42 ... 48 V
3RT1054-1AD36 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1054-1AD36 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 355 A (690 V, 100 kA)
Short-circuit coordination type 2, fusegG: 250 A (690 V, 100 kA), aM: 200 A (690 V, 50 kA), BS88: 250 A (415 V, 50 kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT1054-1AD36 — Connection & Mounting
ParameterValue
Main circuit connectionbox terminal
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, solid or stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew fixing
Side-by-side mountingYes
3RT1054-1AD36 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1054-1AD36 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT1054-1AD36 — Mechanical
ParameterValue
Width120 mm
Height172 mm
Depth170 mm
3RT1054-1AD36 — Specifications
ParameterValue
At AC40 ... 60 ms

Product details

SIRIUS Size S6 Power Contactor, 42-48 V Coil

Rated operating current at 24 V is 10 A; at 48 V it is 2 A; at 110 V it is 1 A; at 220 V it is 0.3 A — these are the auxiliary contact ratings, not the main pole current. The main power circuit accepts stranded conductors from 16 to 70 mm², sized for the S6 frame's full load range.

For BOM freeze or PCN watch, the SIRIUS series has a long production track record; Siemens typically provides 12-18 months notice before any phase-out.

The contactor mounts via screw fixing to a vertical panel surface. Dimensions are 172 mm height, 120 mm width, 170 mm depth — allow the specified clearances: 10 mm upwards, 10 mm downwards, 10 mm at the side, and 20 mm forwards for arc venting and heat dissipation. Power terminals accept stranded 16-70 mm² conductors. Auxiliary/control terminals accept solid or stranded 2x (0.5-1.5 mm²) or 2x (0.75-2.5 mm²), max 2x (0.75-4 mm²). The auxiliary switch is included as standard. Mechanical switching times: arcing time 10-15 ms, closing time at AC/DC 40-60 ms. Maximum operating frequency varies by duty: AC-1 at 800 cycles/hour, AC-3 at 1000 cycles/hour, AC-4 at 130 cycles/hour.

Frequently asked questions

What are the key specifications for 3RT1054-1AD36?

The 3RT1054-1AD36 is a Siemens SIRIUS size S6 power contactor with a 42-48 V AC/DC screw-type coil. It accepts stranded power conductors from 16 to 70 mm², measures 172 x 120 x 170 mm, and operates from -25 to +60 °C. Auxiliary contacts are rated at 10 A at 24 V and 2 A at 48 V.

How do I get current pricing and availability for 3RT1054-1AD36?

Current pricing and availability for the 3RT1054-1AD36 are confirmed at quote time. Submit an RFQ through this listing; the sourcing team will respond with a firm quote and lead time based on current distribution stock.

What is the depth of the 3RT1054-1AD36?

The depth of the 3RT1054-1AD36 is 170 mm. Combined with its 172 mm height and 120 mm width, it requires a minimum enclosure depth of about 190 mm when allowing the 20 mm forward clearance for arc venting.

What wire sizes does the 3RT1054-1AD36 accept?

The main power terminals accept stranded conductors from 16 to 70 mm². The auxiliary/control terminals accept solid or stranded wire: 2x (0.5-1.5 mm²), 2x (0.75-2.5 mm²), or max 2x (0.75-4 mm²).

MPN