Power wiring accepts stranded conductors from 16 to 70 mm².
Ratings and switching performance
The auxiliary contact set carries 10 A at 24 V rated value, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, and 0.3 A at 220 V. Maximum mechanical switching frequency at AC-3 duty is 1 000 operations per hour; at AC-1 it is 800 1/h, at AC-2 it is 400 1/h, and at AC-4 it is 130 1/h. Typical mechanical life of the contactor is 10 000 000 operations. Arcing time is 10-15 ms, and the closing time at AC or DC is 40-60 ms.