Skip to main content
Siemens 3RT1054-2NF36 — Contactors

Siemens SIRIUS 3RT1054-2NF36 Power Contactor, S6, 96-127 VAC

MPN3RT1054-2NF36
Active

Siemens SIRIUS S6 power contactor, 3RT1054-2NF36, 96-127 VAC coil, screw fixing, spring-type coil terminals, 170 mm depth, 172 mm height, 120 mm width.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1054-2NF36 — Identification
ParameterValue
Contactor frame sizeS6
3RT1054-2NF36 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V97 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V25 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1054-2NF36 — Control & Coil
ParameterValue
Control supply voltage typeAC/DC
Rated value @ 50 Hz0.6
Rated value @ 50 Hz96 ... 127 V
3RT1054-2NF36 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1054-2NF36 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 355 A (690 V, 100 kA)
Short-circuit coordination type 2, fusegG: 250 A (690 V, 100 kA), aM: 200 A (690 V, 50 kA), BS88: 250 A (415 V, 50 kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT1054-2NF36 — Connection & Mounting
ParameterValue
Main circuit connectionConnection bar
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid2x (0.25 ... 2.5 mm²)
Conductor cross-section, solid or stranded2x (0,25 ... 2,5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.25 ... 1.5 mm²)
Mounting methodscrew fixing
Side-by-side mountingYes
3RT1054-2NF36 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1054-2NF36 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT1054-2NF36 — Mechanical
ParameterValue
Width120 mm
Height172 mm
Depth170 mm
3RT1054-2NF36 — Specifications
ParameterValue
At AC80 ... 90 ms

Product details

Siemens SIRIUS 3RT1054-2NF36 — Power Contactor, S6 Frame

It carries a 96-127 VAC coil and is fixed via screw mounting with a single 9 mm hole. The coil uses spring-type terminals for fast wiring, while the main power circuit accepts stranded conductors from 25 to 120 mm² — sized for the S6 frame's typical motor currents in the 100+ A range.

Switching Performance and Duty Ratings

The 3RT1054-2NF36 delivers consistent operating times of 80-90 ms on both AC and DC supplies, with an arcing time of 10-15 ms — important for coordinating with upstream protective devices in a motor branch circuit. Maximum switching frequency varies by duty class: 800 operations per hour under AC-1 (resistive loads), 1000 per hour under AC-3 (standard motor starting), and 130 per hour under AC-4 (plugging/reversing).

Auxiliary and Control Circuit Ratings

An auxiliary switch is built into the contactor. Its rated values span: 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, and 1 A at 110 V — covering typical PLC output and relay interface voltages. The coil circuit accepts solid conductors of 2x 0.25-2.5 mm² via spring-cage terminals, matching standard control wiring practice.

Physical Dimensions and Clearance Requirements

The contactor measures 170 mm deep, 172 mm high, and 120 mm wide.

For BOM freeze or second-source planning, the closest peer within the SIRIUS S6 range is the 3RT1054-2AP36, which shares the same frame size and mounting footprint but differs in coil voltage. The 3RT1054-1AB36 and 3RT1055-6QF35 are also S6-frame variants with different coil ratings or auxiliary configurations.

Frequently asked questions

What is the coil voltage for 3RT1054-2NF36?

The coil is rated for 96-127 VAC, with an initial pickup value of 0.8 times the rated voltage.

What are the mounting dimensions and clearances for this contactor?

The contactor measures 170 mm deep, 172 mm high, and 120 mm wide. Minimum clearances: 10 mm up/down/sides, 20 mm forward. Mounting is via screw fixing with a single 9 mm hole.

What is the closest second-source alternative to 3RT1054-2NF36?

The 3RT1054-2AP36 is the closest functional peer within the same S6 frame — it shares the same physical footprint and terminal layout but uses a different coil voltage. Check coil compatibility before substituting.

MPN
3RT1054-2NF36