SIRIUS S6 power contactor with 24 VDC coil
It is rated for the S6 frame size, which determines its footprint and mounting hole pattern for panel integration. The coil draws 6 A at 24 V rated value, with a pickup dropout characteristic typical of DC-operated contactors — the arcing time is 10 to 15 ms and the closing time at DC is 80 to 90 ms. Mechanical switching rates vary by duty: up to 1 000 cycles per hour in AC-3 and AC-3e, 800 in AC-1, 400 in AC-2, and 130 in AC-4. For DC loads, the rates are 400 in DC-1 and 500 in DC-3 and DC-5.
Auxiliary contact DC ratings and terminal details
The auxiliary switch is rated for DC switching at specific voltages: 6 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, and 0.9 A at 125 V. These ratings define the maximum continuous current the auxiliary contacts can break under DC inductive loads. Screw terminals accept 2x (0.25 to 2.5 mm²) solid or stranded wire.
Environmental range and clearances
Dimensions are 172 mm height, 120 mm width, and 170 mm depth — the S6 frame size fits standard panel layouts with screw-fixing compatibility.