It carries a 110 VDC coil and is rated for AC-3 duty at up to 1000 switching cycles per hour, with AC-4 at 130 cycles/h for plugging or inching applications. The 110 VDC coil pull-in and drop-out timing runs 80 to 90 ms at rated voltage, with an arcing time of 10 to 15 ms.
The 172 x 120 x 170 mm (H x W x D) contactor requires minimum clearance around the enclosure: 10 mm upwards, 10 mm downwards, 20 mm forwards, and 10 mm at the side. The single 9 mm mounting hole matches standard M8 hardware. Solid and stranded wire terminations accept 2x 0.25 to 2.5 mm² per clamp — typical for control wiring in a Size S6 panel.