The coil is rated 200-220 V AC at 50/60 Hz, and the main power terminals accept stranded cable from 25 to 120 mm², so this is sized for the higher-current end of the S6 range.
Panel fit and clearances
Footprint is 172 mm high by 120 mm wide by 170 mm deep.
Switching duty and operating rhythm
Maximum switching frequency depends on the duty category: 1 000 operations per hour in AC-3 and AC-3e (the standard motor-starting duty), 800 in AC-1 (resistive), 400 in AC-2 (slip-ring motor starting), and 130 in AC-4 (plugging/inching). For a typical conveyor motor running at AC-3, that's one start every 3.6 seconds at full rate — well within the margin for most line cycles.
Coil and auxiliary contact specs
Coil pickup and dropout timing: 40 to 60 ms on both AC and DC supplies. The auxiliary contact ratings at 24 V are 10 A, dropping to 2 A at 48 V and 60 V, and 1 A at 110 V — these matter when the auxiliary feeds a PLC input or a holding circuit in a safety chain. The coil's full-scale value is 1.1 (likely the pickup multiplier above rated voltage), and the initial value is 0.8 (dropout threshold).