Skip to main content
Siemens 3RT1055-2AD36 — Contactors

Siemens 3RT1055-2AD36 SIRIUS Power Contactor, 42-48 V Coil,

MPN3RT1055-2AD36
Active

Siemens SIRIUS power contactor, size S6, 42-48 V AC/DC coil, screw fixing, 25-120 mm² main circuit conductors, auxiliary switch included.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT1055-2AD36 — Identification
ParameterValue
Contactor frame sizeS6
3RT1055-2AD36 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V132 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V30 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1055-2AD36 — Control & Coil
ParameterValue
Control supply voltage typeAC/DC
Rated value @ 50 Hz0.8
Rated value @ 50 Hz42 ... 48 V
3RT1055-2AD36 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1055-2AD36 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 355 A (690 V, 100 kA)
Short-circuit coordination type 2, fusegG: 315 A (690 V, 100 kA), aM: 200 A (690 V, 50 kA), BS88: 315 A (415 V, 50 kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT1055-2AD36 — Connection & Mounting
ParameterValue
Main circuit connectionConnection bar
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid2x (0.25 ... 2.5 mm²)
Conductor cross-section, solid or stranded2x (0,25 ... 2,5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.25 ... 1.5 mm²)
Mounting methodscrew fixing
Side-by-side mountingYes
3RT1055-2AD36 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1055-2AD36 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT1055-2AD36 — Mechanical
ParameterValue
Width120 mm
Height172 mm
Depth170 mm
3RT1055-2AD36 — Specifications
ParameterValue
At AC40 ... 60 ms

Product details

Siemens SIRIUS 3RT1055-2AD36 — Power Contactor, Size S6

It carries a 42-48 V AC/DC coil (rated value 42-48 V) and includes an auxiliary switch (auxiliary switch yes). The main circuit accepts stranded conductors from 25 to 120 mm² (stranded 25-120 mm²), while the auxiliary circuit takes solid or stranded 2x 0.25-2.5 mm² (solid 2x 0.25-2.5 mm²). Coil termination uses spring-type terminals (of magnet coil spring-type terminals).

Fastened via screw fixing (fastening method screw fixing) through a single 9 mm hole (number of holes 1, diameter of holes 9 mm). Mounting position allows vertical surface with +/-90° rotation and +/-22.5° tilt forward/backward (mounting position with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/-22.5° tiltable to the front and back). Dimensions: width 120 mm, height 172 mm, depth 170 mm (width 120 mm, height 172 mm, depth 170 mm). Clearance distances: upwards 10 mm, downwards 10 mm, forwards 20 mm, at the side 10 mm (upwards 10 mm, downwards 10 mm, forwards 20 mm, at the side 10 mm).

Switching Performance and Endurance

Rated for AC-1 maximum 800 operations per hour (at AC-1 maximum 800 1/h), AC-2 maximum 300 ops/h (at AC-2 maximum 300 1/h), AC-3 maximum 750 ops/h (at AC-3 maximum 750 1/h), AC-3e maximum 750 ops/h (at AC-3e maximum 750 1/h), and AC-4 maximum 130 ops/h (at AC-4 maximum 130 1/h). Arcing time is 10-15 ms (arcing time 10-15 ms). Mechanical endurance typical 10,000,000 operations (of contactor typical 10,000,000). Auxiliary contact ratings: 10 A at 24 V rated value (at 24 V rated value 10 A), 2 A at 48 V (at 48 V rated value 2 A), 2 A at 60 V (at 60 V rated value 2 A), 1 A at 110 V (at 110 V rated value 1 A).

Frequently asked questions

What is the closest functional second-source for 3RT1055-2AD36?

The peer 3RT1055-6QF35 is a similar SIRIUS size S6 contactor, but it uses a 36-42 V coil versus the 42-48 V coil on the 3RT1055-2AD36 — verify coil voltage compatibility before substituting.

What are the key dimensions of 3RT1055-2AD36?

Width 120 mm, height 172 mm, depth 170 mm.

What conductor sizes does 3RT1055-2AD36 accept?

Main circuit accepts stranded 25-120 mm²; auxiliary circuit accepts solid or stranded 2x 0.25-2.5 mm².

Where can I buy 3RT1055-2AD36?

This part is sourced and quoted to order against an RFQ through independent distribution — availability and current pricing are confirmed at quote time.

MPN
3RT1055-2AD36