The coil is wound for 380-420 V AC, and the main power terminals accept stranded cable from 25 to 120 mm² — sized for the higher-current branch circuits this frame serves.
Mounts via screw fixing (9 mm holes) on a vertical surface, rotatable ±90° or tiltable ±22.5° front-to-back. The body measures 172 mm high, 120 mm wide, 170 mm deep — plan the enclosure depth around that 170 mm figure, plus the 20 mm forward clearance for arc venting and the 10 mm side/downward clearances. Coil connections use spring-type terminals (2x 0.25-2.5 mm² solid or stranded), so no screwdriver needed on the control wiring.
Switching Performance & Duty
Arcing time runs 10-15 ms. The contactor handles up to 800 operations per hour in AC-1 (resistive) duty, 750/h in AC-3 (motor start/run), and 130/h in AC-4 (plugging/inching). The auxiliary switch is built in, rated at 10 A at 24 V, 2 A at 48/60 V, and 1 A at 110 V — enough for pilot-duty signaling.
Environmental & Lifecycle
The lifecycle status is listed as current — this is an active catalog item, not a phase-out.