3RT1055-6AV36 - Siemens
power contactor, AC-3e/AC-3 150 A, 75 kW / 400 V AC (50-60 Hz) / DC Uc: 380-420 V 3-pole, auxiliary contacts 2 NO + 2 NC drive: conventional main circuit: busbar control and auxiliary circuit: screw terminal
Specifications
| Parameter | Value |
|---|---|
| Contactor frame size | S6 |
| Parameter | Value |
|---|---|
| Rated operational current, AC-12, max. | 10 A |
| Rated operational current, AC-4 @ 400 V | 132 A |
| Rated value @ 400 V | 3 A |
| Rated value @ 500 V | 2 A |
| Rated value @ 690 V | 1 A |
| Rated value @ 230 V | 30 hp |
| Rated value @ 24 V | 10 A |
| Rated value @ 60 V | 2 A |
| Rated value @ 110 V | 1 A |
| Rated value @ 220 V | 0.3 A |
| Parameter | Value |
|---|---|
| Control supply voltage type | AC/DC |
| Rated value @ 50 Hz | 0.8 |
| Rated value @ 50 Hz | 380 ... 420 V |
| Parameter | Value |
|---|---|
| Main poles | 3 |
| Main NO contacts | 3 |
| Auxiliary contact reliability | 1 faulty switching per 100 million (17 V, 1 mA) |
| Parameter | Value |
|---|---|
| Short-circuit coordination type 1, fuse | gG: 355 A (690 V, 100 kA) |
| Short-circuit coordination type 2, fuse | gG: 315 A (690 V, 100 kA), aM: 200 A (690 V, 50 kA), BS88: 315 A (415 V, 50 kA) |
| Aux. switch short-circuit protection, fuse | gG: 10 A (500 V, 1 kA) |
| Parameter | Value |
|---|---|
| Main circuit connection | Connection bar |
| Aux. / control circuit connection | screw-type terminals |
| Conductor cross-section, solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²) |
| Conductor cross-section, solid or stranded | 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²) |
| Conductor cross-section, finely stranded w/ ferrule | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| Mounting method | screw fixing |
| Side-by-side mounting | Yes |
| Parameter | Value |
|---|---|
| Durability (operating cycles, typ.) | 10 000 000 |
| Durability with aux. switch block (cycles, typ.) | 10 000 000 |
| Parameter | Value |
|---|---|
| Operating temperature range | -25 ... +60 °C |
| Storage temperature range | -55 ... +80 °C |
| Installation altitude, max. | 2 000 m |
| Parameter | Value |
|---|---|
| Width | 120 mm |
| Height | 172 mm |
| Depth | 170 mm |
| Parameter | Value |
|---|---|
| At AC | 40 ... 60 ms |
Frequently asked questions
What is the coil voltage of the Siemens 3RT1055-6AV36 contactor?
Coil suffix (AV36 = 380-420 V AC/DC) determines drive control compatibility and prevents miswiring on the panel.
What back-up fuse rating is required for the 3RT1055-6AV36 at 150 A AC-3?
Coordination with upstream breaker/fuse is mandatory for Type 1/2 protection and panel certification.
Does the Siemens 3RT1055-6AV36 have a mirror contact for safety applications?
Mirror contact per IEC 60947-4-1 is required for safety circuits and SIL/PL claims.
Which auxiliary contact blocks fit the Siemens Sirius 3RT1055 150 A contactor?
Correct aux block part number is needed for 2 NO + 2 NC expansion and SIRIUS ecosystem integration.
What is the difference between 3RT1055-6AV36 and other 3RT1055 variants like 6AF36 or 6AP36?
Coil suffix differences hide real voltage variations that affect interchangeability in installed base spares.
Where can I buy the 3RT1055-6AV36 with stock, lead time and authorized traceability?
Sourcing risk on allocated 150 A Sirius contactors requires verified distributor stock and certificate of conformance.