It uses a 23-26 VDC coil and spring-type terminals on the coil side, with screw fixing for panel mounting. The contactor carries a mechanical life of 10,000,000 operations and an operating temperature range of -25 to +60 °C.
Coil and Control Circuit Details
The coil side wiring uses spring-type terminals accepting 2x (0.25-2.5 mm²) solid or stranded. The main power terminals accept stranded wire from 25 to 120 mm², sized for the S6 frame's current capacity. An auxiliary switch is built in, rated 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, and 1 A at 110 V — enough to signal a PLC input or drive a pilot light.
Mounting is by screw fixing with one 9 mm hole. The contactor can be mounted on a vertical surface, rotatable ±90°, and tiltable ±22.5° forward and backward. Dimensions: 172 mm high, 120 mm wide, 170 mm deep. That 170 mm depth is the front-to-back envelope — factor it into your panel layout, especially if you're retrofitting into an existing enclosure where the backplane is tight.