The main poles accept stranded conductors from 25 to 120 mm², so it lands squarely in heavy motor-switching duty — conveyors, pumps, compressors, anything pulling full-load current in the S6 range.
The built-in auxiliary switch is rated for 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, and 1 A at 110 V. At 48 V, the 2 A figure is typical for a small contactor or indicator load; if you need to drive a heavier solenoid bank at that voltage, you'd want to check the inrush against that 2 A limit.
Thermal environment and mounting clearances
The enclosure needs at least 10 mm clearance upwards, downwards, and at the sides, plus 20 mm forward — tight enough for a standard 600 mm deep panel, but watch the forward clearance if you're mounting a busbar or shield plate close. Dimensions are 170 mm deep, 120 mm wide, 172 mm high.