Fastened via screw fixing through a single 9 mm hole. Envelope is 172 mm high, 120 mm wide, 170 mm deep. Main power circuit accepts stranded cable from 25 to 120 mm². Control circuit (coil + auxiliary) uses screw-type terminals accepting 2x (0.5…1.5 mm²), 2x (0.75…2.5 mm²), or max 2x (0.75…4 mm²) solid or stranded wire. Built-in auxiliary switch (1 N/O + 1 N/C typically) is present — the contactor ships with it, no separate add-on needed for basic status feedback. Its rated current: 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V.
Coil performance and environmental range
Operate time is 80-90 ms on both AC and DC supply. Arcing time runs 10-15 ms. Pick-up voltage is 0.8 x rated (76.8 V minimum), drop-out is 1.1 x rated (139.7 V) — the wide hysteresis means the contactor holds in during sags but drops cleanly when the control signal is removed.