Its 200-277 V AC coil uses screw-type terminals, and the main power circuit accepts stranded cable from 70 up to 240 mm² — sized for the higher-current branch circuits this frame class handles. Mounting position is flexible: vertical surface with ±90° rotation or ±22.5° tilt front-to-back. The contactor is fastened via screw fixing through a single 11 mm hole. Overall dimensions are 210 mm high, 145 mm wide, 202 mm deep.
Duty Cycle and Switching Frequency
Maximum switching frequency depends on the duty category: 800 operations per hour in AC-1 (resistive), 500/h in AC-3 and AC-3e (standard motor starting), 250/h in AC-2 (slip-ring motor), and 130/h in AC-4 (plugging/inching). The arcing time is 10-15 ms.
Its rated breaking capacity at 24 V is 10 A, dropping to 2 A at 48 V and 60 V, and 1 A at 110 V.
Environmental and Clearance
Lifecycle status is current production.