Coil voltage range is 200–277 V AC/DC. Screw-type coil terminals and screw fixing mounting — expect a solid panel mount, not a DIN-rail clip. The contactor carries an auxiliary switch and accepts stranded cable up to 240 mm² on the main poles.
Dimensions: 210 mm high, 165 mm wide, 202 mm deep. The S10 frame is one of the larger contactor footprints — plan for a 202 mm depth behind the panel door.
Duty and switching performance
Switching frequency varies by duty: AC-1 (resistive) up to 800 operations/hour, AC-3 (motor starting) up to 700 ops/h, AC-4 (plugging/inching) up to 130 ops/h. Mechanical life typical: 10 million operations.