SIRIUS S10 power contactor, 110-127 V coil — what you're looking at
The 110-127 V AC coil pulls in down to 0.8 × rated and drops out cleanly; closure time is 40-80 ms. The screw-terminal variant accepts stranded cable from 70 mm² to 240 mm².
The screw fixing method uses an 11 mm hole — one hole, so it's a single-bolt mount, not a four-corner pattern.
Switching duty and mechanical life
Rated for AC-3 motor switching at 500 operations per hour maximum, AC-1 resistive at 750 ops/h, AC-4 (plugging/reversing) at 130 ops/h. The auxiliary switch is included — screw-type terminals on the coil side as well. Arcing time runs 10-15 ms; power factor at 50/60 Hz is 0.9. The auxiliary contact ratings: 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V — enough for a PLC input or a pilot light, but watch the voltage drop on long runs.
