Switching frequency and duty-cycle limits
The 3RT1066-6XB46-0LA2: Maximum switching rates are duty-dependent: 700 operations/hour in AC-1 (resistive), 500/h in AC-3 (motor start/run), 250/h in AC-2 (slip-ring motor), and 130/h in AC-4 (plugging/inching). For DC loads, the ceiling is 350/h in DC-1 and 250/h in DC-3 or DC-5.
The order code 3RT1066-6XB46-0LA2 is the exact Siemens MPN; no direct cross-reference or second-source replacement is documented. Confirm the coil voltage and auxiliary contact configuration match the panel schematic before committing the BOM line.