Mounting Clearances and Wiring
The 3RT1075-6XJ46-0LA2: Mounting position: vertical surface, rotatable ±90°, tiltable ±22.5° front/back. The screw terminals accept 2x (0.5 to 1.5 mm²) solid/stranded, 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) — strip length is not stated in the evidence, but standard practice for this terminal class is 8–10 mm. No DIN-rail clip; this is a bolt-down part.
Switching Performance and Ratings
The DC coil has a rated value of 72 V DC, with an operating range of 0.7 to 1.25 times that (roughly 50 to 90 V DC). Pick-up and drop-out timing: 80 to 100 ms at DC. The auxiliary switch is rated for DC loads: 6 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V. Maximum switching frequencies per duty class: AC-1 (resistive) 500 cycles/h, AC-2 (slip-ring motor) 200 cycles/h, AC-3 (squirrel-cage motor) 500 cycles/h, AC-3e (enhanced AC-3) 500 cycles/h, AC-4 (plugging/inching) 130 cycles/h, DC-1/DC-3/DC-5 all 250 cycles/h.