The 200-220 V AC coil (rated value per) pulls in reliably across that band. Screw fixing means it mounts to a backplate or sub-panel — not a DIN rail — so factor that into your enclosure layout before the panel build window closes.
The Size S12 frame carries the main pole termination: stranded cable 70-240 mm² for the power circuit, with solid/stranded auxiliary terminals accepting 2x 0.25-2.5 mm². That main lug range covers most motor feeds up to roughly 200-250 A class, but confirm your cable size against the lug window before the outage shift.
Screw fixing to a vertical mounting surface; the contactor can be rotated ±90° or tilted ±22.5° front-to-back. Those clearances are for arc flash and heat dissipation — don't compress them in a tight enclosure or the switching frequency ratings (AC-1 max 500 ops/h, AC-3 max 420 ops/h) will need derating above 40 °C ambient.