The coil is rated 240-277 V AC, with pickup at 80% of rated value, so it stays pulled in across typical line sags. Mechanical life is 10 million cycles typical, and the contactor is rated for AC-1 (500 operations/hour), AC-2 (170/h), AC-3 (420/h), and AC-4 (130/h) duty — the AC-3 figure governs motor switching, so you can run a conveyor or pump at that rate without oversizing.
Main power terminals accept stranded copper from 70 to 240 mm² — that's a heavy cable range, sized for the S12 frame's current capacity. Auxiliary contacts are present and rated: 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V — check the load type against those limits.