Skip to main content
Siemens 3RT1264-6NF36

Siemens 3RT1264-6NF36 SIRIUS Vacuum Contactor, S10

MPN 3RT1264-6NF36
Active

Siemens SIRIUS 3RT1264-6NF36 vacuum contactor, size S10, 96-127 V AC/DC magnet coil, screw-type terminals, screw fixing, main pole stranded 70-240 mm².

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RT1264-6NF36 specifications
ParameterValue
Mountingscrew fixing
Depth206 mm
Width145 mm
Height210 mm
Arcing time10 ... 15 ms

Product details

What this SIRIUS vacuum contactor is and where it fits

The Siemens 3RT1264-6NF36 is a SIRIUS-branded vacuum contactor in the S10 frame size, designed for switching motor loads in industrial control panels where high switching frequency and long mechanical life are required. The vacuum arc-quenching technology means the contacts switch in a sealed vacuum bottle, giving it a typical mechanical endurance of 10,000,000 operations. The coil is rated for 96-127 V AC/DC, with screw-type terminals for the magnet coil connection. Main pole wiring accepts stranded conductors from 70 mm² up to 240 mm², making it suitable for high-current motor circuits.

Mounting and panel integration constraints

Fastening is by screw fixing through a single 11 mm diameter hole. The contactor measures 210 mm high, 145 mm wide, and 206 mm deep. Mounting position allows ±22.5° rotation on a vertical surface, and it can be tilted forward/backward by ±22.5° on a vertical surface, or mounted standing on a horizontal surface. Minimum clearances around the contactor: 10 mm upwards, 20 mm forwards, 10 mm downwards, and 10 mm at the side. These are the air and creepage distances needed for the rated voltages — plan your enclosure layout accordingly.

Switching performance and duty cycle limits

Maximum switching frequency varies by duty class: 800 operations/hour in AC-1 (resistive), 300/h in AC-2, 750/h in AC-3 and AC-3e, and 250/h in AC-4 (plugging/inching). The arcing time is 10-15 ms, and the operating time for both AC and DC coil supply is 80-100 ms. The auxiliary switch is present, with rated values of 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, and 1 A at 110 V. These are the contact ratings for the built-in auxiliary contacts — size your control circuit loads against these limits.

Environmental operating range and lifecycle status

Operating temperature range is -25 to +60 °C; storage range is -55 to +80 °C. The power factor is 0.4 at both 50 Hz and 60 Hz. The initial operating value is 0.8 of rated voltage, and the full-scale value is 1.1 — this defines the coil pick-up and drop-out voltage window.

MPN
3RT1264-6NF36