Siemens 3RT1266-6AF36 — Contactors

Siemens SIRIUS 3RT1266-6AF36 Vacuum Contactor, S10, 110-127

MPN3RT1266-6AF36
Active

Siemens SIRIUS, vacuum contactor, S10 size, 3RT1266-6AF36, 110-127 VAC coil, screw fixing, 210 mm height, 145 mm width, 206 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT1266-6AF36 — Identification
ParameterValue
Contactor frame sizeS10
3RT1266-6AF36 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V280 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1266-6AF36 — Control & Coil
ParameterValue
Control supply voltage typeAC/DC
Rated value @ 50 Hz0.9
Rated value @ 50 Hz110 ... 127 V
3RT1266-6AF36 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1266-6AF36 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 500 A (690 V, 100 kA)
Short-circuit coordination type 2, fusegG: 500 A (690 V, 100 kA), aM: 400 A (690 V, 50 kA), BS88: 450 A (415 V, 50 kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT1266-6AF36 — Connection & Mounting
ParameterValue
Main circuit connectionConnection bar
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, solid or stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew fixing
Side-by-side mountingYes
3RT1266-6AF36 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1266-6AF36 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT1266-6AF36 — Mechanical
ParameterValue
Width145 mm
Height210 mm
Depth206 mm
3RT1266-6AF36 — Specifications
ParameterValue
At AC40 ... 80 ms

Product details

Vacuum-bottle construction means the arc extinguishes in a sealed chamber, so contact erosion is minimal even on high-cycle applications like conveyors or compressors. Coil pulls in on 110-127 VAC, with a pick-up threshold of 0.8 x rated value and dropout around 0.1 x rated value, so it's forgiving on saggy lines.

Power wiring lands on terminals rated for 70 to 240 mm² stranded copper — that's a serious conductor, sized for the full rated current of the S10 frame. The contactor handles up to 750 switching operations per hour in AC-1 (resistive) and AC-3 (motor) duty, and 250 ops/h in AC-2 and AC-4 (slip-ring motor and plugging/inching). Arcing time runs 10-15 ms, with opening times of 40-80 ms on both AC and DC control — fast enough for most motor-starting applications without nuisance tripping from inrush.

Mounts via screw fixing through an 11 mm hole. Keep 10 mm clearance above and below, 20 mm forward, 10 mm to the sides for arc venting and airflow.

Frequently asked questions

How do I get current pricing and availability for 3RT1266-6AF36?

Submit an RFQ through this listing. We source and quote this part to order against your request, with availability and pricing confirmed at quote time.

What is 3RT1266-6AF36's listed depth?

Depth is 206 mm, with a height of 210 mm and width of 145 mm.

What power wiring does 3RT1266-6AF36 accept?

The main power terminals accept stranded copper from 70 mm² up to 240 mm². Auxiliary terminals take 0.5-4 mm² solid or stranded.

MPN
3RT1266-6AF36