Mounting and wiring — panel fit
Screw terminals on the main circuit accept 2x (0.5 to 1.5 mm²) solid, 2x (0.75 to 2.5 mm²) stranded, or up to 2x 4 mm². AWG equivalents: 2x (20–16), 2x (18–14), 1x 12. Finger-safe IP20 on the front and terminals.
Auxiliary contact ratings are also on the nameplate: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V — all at 50/60 Hz. That 10 A AC-12 figure is also the maximum operating current for the main contacts in resistive service. For short-circuit protection with Type 2 coordination, use a gL/gG fuse rated 20 A; Type 1 coordination allows up to 35 A.