The screw-type terminals accept up to 2x 4 mm² per pole, and the 45 mm wide body snaps onto a 35 mm DIN rail per EN 50022.
Side-by-side mounting is permitted with 6 mm spacing at the side. Front and terminal protection is IP20, so it's suitable for enclosed panel installation where accidental finger contact is the concern — not washdown environments.
For type 2 coordination (contactor remains operational after a fault), use gL/gG 20 A. The auxiliary contact block carries 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V — enough for PLC-level signal switching or small relay loads.