Ratings and coordination
Rated for pollution degree 3, operating ambient -25 to +60 °C, and altitude up to 2 000 m without derating. For type 1 coordination a 35 A gL/gG fuse is required; for type 2 coordination a 20 A gL/gG fuse. The DC magnet coil draws 3.3 W holding power — verify the control transformer sizing for multiple contactors on the same 24 VDC supply.
This part carries a current lifecycle status. No official successor has been announced — the 3RT1316-2BM40 remains the active order code for this configuration.