Siemens 3RT1316-2BW40 — Contactors

Siemens 3RT1316-2BW40 SIRIUS Contactor, 48 VDC Coil, 4 NO

MPN3RT1316-2BW40

Siemens SIRIUS power contactor, size S00, 3RT1316-2BW40, 48 VDC coil, 4 NO main contacts, spring-loaded terminals, 10 A AC-12, 45 mm width.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1316-2BW40 — Identification
ParameterValue
Contactor frame sizeS00
3RT1316-2BW40 — Ratings & Performance
ParameterValue
Rated value @ 400 V3 A
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1316-2BW40 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT1316-2BW40 — Contacts & Poles
ParameterValue
Main poles4
Main NO contacts4
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1316-2BW40 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1316-2BW40 — Connection & Mounting
ParameterValue
Main circuit connectionspring-loaded terminals
Conductor cross-section, solid2x (0.25 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.25 ... 1.5 mm²)
Side-by-side mountingYes
3RT1316-2BW40 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1316-2BW40 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1316-2BW40 — Mechanical
ParameterValue
Width45 mm
Height60 mm
Depth72 mm

Product details

What this contactor is and who it's for

The 48 VDC coil pulls 10 A at pickup and holds at 3.3 W, with a pick-up threshold of 0.85x rated voltage and drop-out at 1.1x — meaning it reliably engages at 40.8 V and stays sealed until the supply rises above 52.8 V. For motor switching in AC-2 duty at 400 V, it handles 4 kW, which covers small pumps and fans. For resistive loads (AC-1), it switches 6 A at 230 V and 3 A at 400 V. The AC-12 maximum operating current is 10 A, so it can also serve as a coupler for PLC outputs driving smaller contactor coils.

Termination and wiring

Main circuit connections use spring-loaded terminals accepting 2x (0.25 to 2.5 mm²) solid or 2x (0.25 to 1.5 mm²) fine-stranded with ferrules, or 2x (24 to 14 AWG). The IP20 protection on the front and terminals means it's safe for finger contact inside a closed panel.

For Type 1 coordination (no damage but may need replacement after a fault), use a 35 A gL/gG fuse. For Type 2 coordination (no welding and immediate reuse), use a 20 A gL/gG fuse.

Frequently asked questions

What conductor sizes does the spring terminal accept?

Solid conductors: 2x (0.25 to 2.5 mm²). Fine-stranded with ferrules: 2x (0.25 to 1.5 mm²). AWG: 2x (24 to 14).

Can this contactor be mounted side-by-side without gaps?

Yes, side-by-side mounting is permitted with zero side clearance required, so you can pack units directly adjacent on the DIN rail.

What fuse sizes are recommended for short-circuit coordination?

Type 1 coordination: 35 A gL/gG. Type 2 coordination: 20 A gL/gG.

MPN
3RT1316-2BW40