Skip to main content
Siemens 3RT1317-1AD00 — Contactors

Siemens 3RT1317-1AD00 SIRIUS Power Contactor, S00, 4 NO, 5.5

MPN3RT1317-1AD00

Siemens SIRIUS power contactor, size S00, 4 NO main contacts, 5.5 kW at AC-2 400 V, screw terminals, 45 mm wide, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1317-1AD00 — Identification
ParameterValue
Contactor frame sizeS00
3RT1317-1AD00 — Ratings & Performance
ParameterValue
Rated value @ 400 V3 A
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1317-1AD00 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz42 V
3RT1317-1AD00 — Contacts & Poles
ParameterValue
Main poles4
Main NO contacts4
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1317-1AD00 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 35 A
Short-circuit coordination type 2, fusefuse gL/gG: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1317-1AD00 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1317-1AD00 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1317-1AD00 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1317-1AD00 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth72 mm

Product details

Integrator's first look

The Siemens 3RT1317-1AD00 is a SIRIUS power contactor in the S00 frame size — the smallest footprint in the family at 45 mm wide, 57.5 mm high, and 72 mm deep. Screw-type terminals accept 2x (0.5 to 1.5 mm²) solid or 2x (0.75 to 2.5 mm²) stranded, with a maximum of 2x (0.75 to 4 mm²).

The 5.5 kW at AC-2 400 V rating is the motor-switching figure that governs real-world use — AC-2 covers slip-ring motors and other loads where the contactor makes and breaks at full load. For resistive loads (AC-1), the same contactor handles up to 10 A continuous. The 4 NO main contact arrangement means this contactor closes all four poles simultaneously; there are no NC main contacts on this variant. Short-circuit coordination is specified: Type 2 coordination requires a 20 A gL/gG fuse, while Type 1 allows a 35 A fuse — important for selectivity studies in the panel. Auxiliary contact ratings span 10 A at 24 V up to 0.3 A at 220 V, covering typical PLC and relay interface voltages. The contactor is approved for side-by-side mounting without derating, which saves panel space when multiple contactors are ganged.

At 45 mm wide, this S00 contactor occupies a single 45 mm slot on a DIN rail. Screw terminals are clearly marked and accept ferruled conductors; strip length for the main circuit terminals is approximately 10 mm. The IP20 rating means the contactor is touch-safe out of the box — no additional terminal covers are needed for standard panel builds.

Frequently asked questions

What are the key ratings for the 3RT1317-1AD00?

It is a SIRIUS power contactor, size S00, with 4 NO main contacts. Motor switching rating is 5.5 kW at AC-2 400 V. Resistive load rating is 10 A at AC-1. Mechanical endurance is 30 million operations. Operating temperature range is -25 to +60 °C.

What wire sizes does the 3RT1317-1AD00 accept?

Screw terminals accept 2x (0.5 to 1.5 mm²) solid, 2x (0.75 to 2.5 mm²) stranded, and a maximum of 2x (0.75 to 4 mm²). AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12.

What is the mounting method for the 3RT1317-1AD00?

It mounts via screw or snap-on onto a 35 mm standard mounting rail per DIN EN 50022. Side-by-side mounting is permitted without derating.

What short-circuit protection is required for the 3RT1317-1AD00?

For Type 2 coordination, use a 20 A gL/gG fuse. For Type 1 coordination, a 35 A gL/gG fuse is permitted.

MPN