It carries 4 normally open main contacts and is rated 5.5 kW at 400 V in AC-2 duty (slip-ring motor start/run) and 10 A in AC-12 duty (resistive loads). The coil holds at 42 V DC, with a closing and holding power of 3.3 W.
The screw-type terminals accept solid or stranded copper: 2x (0.5–1.5 mm²), 2x (0.75–2.5 mm²), or max 2x (0.75–4 mm²). AWG equivalents: 2x (20–16), 2x (18–14), or 1x 12. IP20 on the front and terminals — suitable for enclosed panels, not washdown areas.
Coordination and ratings
For Type 1 coordination, use a gL/gG fuse rated 35 A; for Type 2, use 20 A. The contactor is rated for 30 million mechanical operations typical. Altitude limit: 2 000 m. Pollution degree 3.