It is rated for AC-2 motor duty at 5.5 kW on a 400 V supply, with a maximum AC-12 resistive switching current of 10 A.
Ratings and coordination
The AC-12 resistive rating of 10 A covers heater or lighting loads. Short-circuit protection requires a gL/gG fuse: 20 A for type 2 coordination (no welding after fault), 35 A for type 1 (welding allowed but no fire risk). The coil is DC-operated with a closing and holding power of 3.3 W, rated at 220 V DC.
Termination and mounting
Screw terminals accept solid or finely stranded conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²). AWG equivalents for main contacts are 2x (20 to 16), 2x (18 to 14), or 1x 12. Maximum installation altitude is 2 000 m above sea level.