Skip to main content
Siemens 3RT1325-1AV60 — Contactors

Siemens 3RT1325-1AV60 SIRIUS Power Contactor, 4-pole, 7.5 kW

MPN3RT1325-1AV60

Siemens SIRIUS, power contactor, Size S0, 4-pole, 4 NO main contacts, 7.5 kW at 400 V AC-2, screw terminals, 61 mm width, 85 mm height, 91 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1325-1AV60 — Identification
ParameterValue
Contactor frame sizeS0
3RT1325-1AV60 — Ratings & Performance
ParameterValue
Rated value @ 400 V3 A
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1325-1AV60 — Control & Coil
ParameterValue
Control supply voltage typeAC
3RT1325-1AV60 — Contacts & Poles
ParameterValue
Main poles4
Main NO contacts4
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1325-1AV60 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 63 A
Short-circuit coordination type 2, fusefuse gL/gG: 25 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1325-1AV60 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1325-1AV60 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1325-1AV60 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1325-1AV60 — Mechanical
ParameterValue
Width61 mm
Height85 mm
Depth91 mm

Product details

SIRIUS 3RT1325-1AV60 — 4-pole power contactor, Size S0

Its AC-2 motor-switching rating is 7.5 kW at 400 V — that is the figure that governs real motor duty, not the higher AC-1 resistive current. For a 4-pole contactor this frame size, the AC-2 rating tells you the contactor is designed for slip-ring motor starting, where the inrush and breaking duty are heavier than a standard squirrel-cage start. The 61 mm width and 85 mm height keep it within the S0 footprint — plan side clearance of 6 mm for heat dissipation between units.

Auxiliary contact ratings and coordination

The auxiliary contact block (integrated in this variant) is rated across common control voltages: 10 A at 24 V, 6 A at 230 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V, and 3 A at 400 V. These are the make/break capacities for the control circuit — useful when selecting the contactor for a PLC output or a relay interposing. For short-circuit protection, type 1 coordination calls for a 63 A gL/gG fuse; type 2 coordination (where the contactor must remain usable after a fault) requires a 25 A gL/gG fuse.

No official successor has been issued for this code, so the 3RT1325-1AV60 remains the direct fit for any panel built around the S0 frame with 4-pole, 4 NO main contacts and screw terminals.

Wiring and terminal data

Main circuit terminals accept solid or stranded conductors: 2x (1 to 2.5 mm²), 2x (2.5 to 6 mm²), or max 2x 10 mm². Auxiliary terminals accept 2x (0.5 to 1.5 mm²) solid, 2x (0.75 to 2.5 mm²) finely stranded with ferrule, or max 2x (0.75 to 4 mm²). AWG equivalents for main contacts are 2x (20 to 16), 2x (18 to 14), 1x 12; for auxiliary contacts the same AWG ranges apply.

Frequently asked questions

What is the AC-2 motor rating of 3RT1325-1AV60?

The AC-2 rating is 7.5 kW at 400 V, which is the relevant figure for slip-ring motor switching. The contactor also carries AC-12 ratings for resistive loads at 10 A maximum.

Where can I buy 3RT1325-1AV60 and get current pricing?

This part is sourced and quoted to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

Does 3RT1325-1AV60 use screw terminals or spring-cage?

The main current circuit uses screw-type terminals. Auxiliary terminals also use screw connections.

MPN
3RT1325-1AV60